MMP
Pipes
(F-1)
MMP CPVC Pipes Based On ASTM F 441 Pressure Rating Applies for
Water at 23°C and for Unthreaded Pipes
|
Normal
Size
In Inch |
Outside Diameter |
Schedule 80
Minimum Wall Thickness |
Normal
Weight
Kg. / m |
Water
Pressure Rating |
|
Inch |
mm |
Inch |
mm |
Psi |
bar |
|
1/4 |
0.540 |
13.7 |
0.119 |
3.02 |
0.230 |
1130 |
77.8 |
|
1/2 |
0.840 |
21.34 |
0.147 |
3.73 |
0.337 |
850 |
58.6 |
|
3/4 |
1.050 |
26.67 |
0.154 |
3.91 |
0.457 |
690 |
47.6 |
|
1 |
1.315 |
33.40 |
0.179 |
4.55 |
0.671 |
630 |
43.4 |
|
1
1/4 |
1.660 |
42.20 |
0.191 |
4.85 |
0.928 |
520 |
45.9 |
|
1
1/2 |
1.900 |
48.30 |
0.200 |
5.08 |
1.13 |
470 |
32.4 |
|
2 |
25.375 |
60.33 |
0.218 |
5.54 |
1.56 |
400 |
27.6 |
|
3 |
3.500 |
88.9 |
0.300 |
7.62 |
2.9 |
370 |
25.5 |
|
4 |
4.500 |
114.3 |
0.337 |
9.52 |
4.3 |
320 |
22.1 |
|
6 |
6.625 |
168.3 |
0.432 |
10.97 |
8.1 |
280 |
19.3 |
|